WT MECHANICAL AND ELECTRICAL SPECIFICATION

MECHANICAL AND ELECTRICAL SPECIFICATION

 

Minimum flow m³/hr

4

6

8

12

18

25

32

51

75

 

Maximum flow m³/hr

12

19

25

40

60

80

105

165

245

 

No. of fans

1

2

1

1

1

1

1

1

1

 

Fan kW – each

0.75

0.75

0.75

1.1

1.5

2.2

4.0

7.5

11

 

Weight – dry                      kg

40

70

150

210

230

410

510

770

1020

 

Weight – operating            kg

150

234

400

620

900

1230

1600

3870

5520

 

Length                              mm

820

1120

1040

1290

1560

1810

2060

2560

3060

 

Width                               mm

820

820

1040

1290

1560

1810

2060

2560

3060

 

Height                              mm

1840

1840

2810

2885

2920

2930

3060

3960

3960

 

Immersion heater             kW

1

1

3

3

3

3

3

6

6

 

Fan motor start current (each)

11

11

11

14

20

31

55

129

146

 

Fan motor FLC (each)

2.1

2.1

2.1

3.4

4.3

5.7

9.2

17.9

26

 

Heater current per phase
- per heater

 

4.2

 

4.2

 

12.5

 

12.5

 

12.5

 

12.5

 

12.5

 

8.4

 

8.4

 

Noise level at 3 metres

65

66

68

68

70

71

72

77

72

MOTOR DATA                                                                                                                                   HEATER DATA
D.O.L. – all models .415V-3-50Hz                               Unit shipped in two sections                     1.3kW     =    240V-1-50Hz
Speeds   000-01     =   1400 rpm                                   requiring on-site assembly.                           6kW     =    415V-3-50Hz
02-04     =     930 rpm
05-06     =     720 rpm