close this window

VP PHYSICAL & ELCTRICAL DATA

 

VP Range

2

6

9

12

15

22

30

45

60

75

90

105

120

Nominal duty at 10°C
LWT – 28°C amb

kW

2

6

9

12

15

22

30

45

60

75

90

105

120

Nominal flow EWT
15°C-LWT – 10°C

m3/hr

0.35

1.03

1.55

2.06

2.58

3.79

5.16

7.74

10.32

12.9

15.48

18.06

20.64

Evaporator pressure
drop at 5°C

m.HD

3

3

4.5

6.8

5.3

6.8

5.7

6.8

6.8

6.8

6.8

6.8

6.8

 

No. off
Compressors

Fully
hermetic

1

1

1

1

1

1

1

1

1

2

2

2

2

Semi
hermetic

-

-

-

-

-

-

-

Opt

Opt

Opt

Opt

Opt

Opt

Compressor nominal
Input (each)

KW

1.18

2.6

3.8

4.6

5.7

8.3

12.5

16.7

25.3

14.25

16.7

20.2

25.3

Refrigeration circuits

1

1

1

1

1

1

1

1

1

1

1

1

1

 

Capacity control

%

0

 

100

0

50
100

0

50
100

0

50
100

0

50
100

0

50
100

0

50
100

0

50
100

0

50
100

0
25
50
100

0
25
50
100

0
25
50
100

0
25
50
100

Air flow

M3/hr

2000

6000

7000

7000

12000

11000

12000

24000

24000

36000

36000

48000

48000

No. off fans

1

1

1

1

1

1

1

2

2

3

3

4

4

Fan (each)

KW

0.06

0.45

0.45

0.45

1.1

1.1

1.5

1.5

1.5

1.5

1.5

1.5

1.5

Full load current

A

8.8

11.7

16.7

16.9

18.7

24.3

30.4

45.2

64.1

74.3

83.3

105

127

Max. start current DOL

A

38

49

64

77

101

109

152

200

271

180

205

267

292

Noise level at 2 metres

dBA

66

68

70

70

70

72

74

77

77

80

80

83

83

Dual circuit refrigeration models available.