VP Range |
|||||||||||||
2 |
6 |
9 |
12 |
15 |
22 |
30 |
45 |
60 |
75 |
90 |
105 |
120 |
||
Nominal duty at 10°C |
kW |
2 |
6 |
9 |
12 |
15 |
22 |
30 |
45 |
60 |
75 |
90 |
105 |
120 |
Nominal flow EWT |
m3/hr |
0.35 |
1.03 |
1.55 |
2.06 |
2.58 |
3.79 |
5.16 |
7.74 |
10.32 |
12.9 |
15.48 |
18.06 |
20.64 |
Evaporator pressure |
m.HD |
3 |
3 |
4.5 |
6.8 |
5.3 |
6.8 |
5.7 |
6.8 |
6.8 |
6.8 |
6.8 |
6.8 |
6.8 |
No. off |
Fully |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
2 |
2 |
2 |
2 |
Semi |
- |
- |
- |
- |
- |
- |
- |
Opt |
Opt |
Opt |
Opt |
Opt |
Opt |
|
Compressor nominal |
KW |
1.18 |
2.6 |
3.8 |
4.6 |
5.7 |
8.3 |
12.5 |
16.7 |
25.3 |
14.25 |
16.7 |
20.2 |
25.3 |
Refrigeration circuits |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
|
Capacity control |
% |
0
100 |
0 50 |
0 50 |
0 50 |
0 50 |
0 50 |
0 50 |
0 50 |
0 50 |
0 |
0 |
0 |
0 |
Air flow |
M3/hr |
2000 |
6000 |
7000 |
7000 |
12000 |
11000 |
12000 |
24000 |
24000 |
36000 |
36000 |
48000 |
48000 |
No. off fans |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
2 |
2 |
3 |
3 |
4 |
4 |
|
Fan (each) |
KW |
0.06 |
0.45 |
0.45 |
0.45 |
1.1 |
1.1 |
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
Full load current |
A |
8.8 |
11.7 |
16.7 |
16.9 |
18.7 |
24.3 |
30.4 |
45.2 |
64.1 |
74.3 |
83.3 |
105 |
127 |
Max. start current DOL |
A |
38 |
49 |
64 |
77 |
101 |
109 |
152 |
200 |
271 |
180 |
205 |
267 |
292 |
Noise level at 2 metres |
dBA |
66 |
68 |
70 |
70 |
70 |
72 |
74 |
77 |
77 |
80 |
80 |
83 |
83 |
| Dual circuit refrigeration models available. |